SAMSUNG Multi outdoor unit
ECO S-Inverter Multi
whisper-quiet
Cooling, heating, dehumidifying, ventilating
Cooling mode down to - 5°C, heating mode down to -20°C
The nominal output can be exceeded by up to 50%.
Depending on the system, up to 5 indoor units can be connected
Circuit board with alphanumeric display for exact diagnoses
Auto restart
All cooling units comply with the Eco standard and have best SEER and SCOP values
Only one power supply. The indoor units are supplied via the refrigerating machine
Automatic addressing
The Free Joint Multi Inverter cooling machine has a weatherproof sheet steel housing with a torsion-free base frame for outdoor installation. Equipped with a TWIN BLDC inverter rotary piston compressor, vibration-damped, extremely quiet and energy-saving. Newly developed sickle-shaped fan, directly driven and electronically balanced ensures whisper-quiet operation. The refrigeration system is prefilled with R32 safety refrigerant at the factory. The ideal solution for air-conditioning various rooms with different indoor units from the Free Joint Multi series with a super-quiet, compact cooling machine.
In terms of system control and communication, this cooling machine is compatible with all Samsung DVM Multi systems. This means that it can be integrated into the control of DVM systems without the need for an additional board.
Marke / Model | SAMSUNG / AJ100MCJ5EH/EU |
Cooling capacity min/standard/max (kW): | 5,0 / 10,0 / 17,3 |
Heating capacity Min/Standard/Max (kW): | 6,0 / 12,0 / 21,0 |
Technical data : | |
Anzahl indoor unite (Min / Max): | 2-5 |
AnschlussPower indoor unite cooling, Min / Max (kW): | 5,0 / 17,3 |
AnschlussPower indoor unite Heizen, Min / Max (kW): | 6,0 / 21,0 |
S.E.E.R: | 6,0 |
S.C.O.P: | 4,0 |
Wirkungsgrad: | |
Energieeffizienz cooling Klasse: | A+ |
Energieeffizienz Keizen Klasse: | A+ |
Einsatzbereich : | |
Außentemperatur Cooling mode (°C): | -5 bis +46 |
Außentemperatur Heizbetrieb (°C): | -15 bis +24 |
Elektrische Daten : | |
Power supply (V / Ph / Hz): | 240 / 1 / 50 |
Absicherung, träge (A): | 20 |
Power consumption cooling / Heizen (kW): | 2,9 / 2,93 |
Operating current Max (A): | 13,4 |
Kabel Ø, Einspeisung gem. VDE z. Kühlmaschine (mm²): | NYM 3 x 2,5 |
Kabel Ø Einspeisung indoor unit ü. Außengerät (mm²): | NYM 3 x 1,5 + Busleitung LIYCY 2x 2 x 0,75 |
Regelung, Ventilator, Maße, Weight:e : | |
Selbstdiagnosesystem : | ja |
Ventilator (Stück): | 1 |
Luftmenge max (m³/h): | 4234 |
Sound pressure level (dB(A)): | 54 |
SchallPowerspegel (dB(A)): | 70 |
Dimensions (HxBxT) (mm): | 998x940x330 |
Weight (kg): | 75 |
Pipe-Check-Funktion: | ja |
Coolingmittelleitungen : | |
Liquid keitsleitung (Ø Zoll): | 5x 1/4" |
Sauggasleitung (Ø Zoll): | 2x 3/8" / 3x 1/2" |
Coolingmittelverteiler erforderlich: | No |
Wärmeisolierung (beide Leitungen): | Ja |
Equivalente Leitungslänge Außen- / indoor unit, max (m): | ~25 |
Gesamtrohrleitungslänge Außen- / indoor unite, max (m): | 80 |
Height difference, Außengerät höher/tiefer, max (m): | 15 |
Coolingmittel: | R410A |
Coolingmittelmenge werkseitig vorgefüllt (kg / tCO e): | 3,30 / 6,89 |
Coolingmittelfüllung f. max. Leitungslänge bis (m): | 40 |
Coolingmittelnachfüllung für Mehrmeter (g/m): | 20 |
Coolingmitteleinspritzung EEV, Außengerät (steps): | 480 |
Optional und Digital | |
Systemmanagement via Internet und DMS: | Ja |
Energieerfassung- / abrechnung: | Ja |
Systemanbindung an GLT (Gebäudeleittechnik): | LonWorks - BACnet - Modbus - KNX-EIB |